The limiting pressure drop, defined in ANSI/ISA-75.01.01-2012 (60534-2-1 MOD) as “ΔP(choked)” is the dividing line between non-choked flow and choked flow shown on the above graph. Prior to the current edition, the standards did not give a name to this dividing line. Consequently, valve manufacturers have used different names for the same thing, some of which are also shown in the figure.
The entire subject of liquid flow in control valves, choked flow, cavitation and flashing including prediction and prevention techniques are covered in detail in Neles’ “Flow Control Manual” and Valin Corporation’s book “Control Valve Application Technology.”
This blog addresses the issue of determining the vapor pressure of the process liquid, which is part of the calculation of ΔP(choked) in the following equation:
ΔP(choked) = FL2(P1 – FF PV) where PV is the liquid’s vapor pressure, which depends on the particular liquid and its temperature.
I am constantly asked by valve users what the vapor pressure of a particular liquid is. For water-based chemicals, using the vapor pressure of water will give a conservative value of PV and there are tables of water vapor pressure readily available in many sources. Also, most of the available software for control valve sizing, including Nelprof, will automatically include the water vapor pressure for the given temperature. Nelprof can also calculate vapor pressures for 29 other chemicals that are listed in its database. For many other chemicals, published vapor pressure data is scarce.
There are a number of calculation methods for liquid vapor pressure, but most are too complex for hand calculations, and require the input of chemical properties that are not always readily available. The simplest calculation method is the Antoine equation. The only problem is finding comprehensive tables of Antoine equation parameters. Any set of Antoine parameters (A, B and C) is only valid for a limited range of temperatures, and many of the tables of parameters I have seen only include parameters for one temperature range. Some tables, which only include one set of constants, do not tell you what the valid temperature range is, which can lead to unreliable calculation results. The best database that I have found that is available at no charge (at least at the present time) is the NIST (National Institute of Standards and Technology) Chemistry WebBook, which can be found at: http://webbook.nist.gov/chemistry/.
The Antoine parameters given in the WebBook are for temperature in degrees Kelvin, and return a vapor pressure in bar. You can carry out the calculations by hand or you can construct an Excel® worksheet to make the calculations. As an alternate, you can use the Excel sheet I have made, that lists step-by-step instructions for finding the Antoine parameters in the NIST Chemistry DataBook. It converts your temperature, that you most likely know in degrees F or C, to degrees K which is required by the NIST Antoine formula, and it returns the calculated vapor pressure in both bar and psia. You can download the Excel sheet free of charge from the “Worksheet” tab at: http://www.control-valve-application-tools.com/.
This blog post has been up-dated in July 2020, due to company name change to Neles.